Technical Parameter
Structure、Size Parameter Table No. | Type | Structure Height mm | Min. Creepage Distance mm | Min. Nominal Creepage Distance mm | Umbrella Diameter mm | Thread Length mm | Applicable Wire Cross Section mm² |
1 | FZJH10-95/25 | 400±15 | 185 | 480 | 150/120±0.5 | M20x40 | 25~95 |
2 | FZJH10-185/95 | 400±15 | 185 | 480 | 150/120±0.5 | M20x40 | 95~185 |
3 | FZJH10-240/150 | 400±15 | 185 | 480 | 150/120±0.5 | M20x40 | 150~240 |
4 | FZJH10-240/240 | 400±15 | 185 | 480 | 150/120±0.5 | M20x40 | 240 |
No. | Type | Rated Mechanical Load kN | Lightning Impulse Withstand Voltage(peak) kV | Industrial frequency dry withstand voltage(rms) kV | Industrial frequency wet withstand voltage(rms) kV | Nom. Current A | Dynamic Stability Test DL/T879-2004 | Thermal Stability Test DL/T879-2004 |
1 | FZJH10-95/25 | 4 | ≥75 | ≥42 | ≥50 | 476 | ≤18.3kA 0.1s | 7.3kA/1°-5%S |
2 | FZJH10-185/95 | 4 | ≥75 | ≥42 | ≥50 | 476 | ≤18.3kA 0.1s | 7.3kA/1°-5%S |
3 | FZJH10-240/150 | 4 | ≥75 | ≥42 | ≥50 | 476 | ≤25.6kA 0.1s | 7.3kA/1°-5%S |
4 | FZJH10-240/240 | 4 | ≥75 | ≥42 | ≥50 | 476 | ≤25.6kA 0.1s | 7.3kA/1°-5%S |